    User name T. Badman

    Log entry time 11:21:45 on April 22, 2012

    Entry number 377451

    This entry is a followup to: 377442

    keyword=target amp fault

    What is likely happening is when you move the target to one extreme (top 
    cell) and add such a large offset the encoder will think you are on the 
    wrong side of the limit switch. Trying to move away from that position 
    would cause a fault when it then tries to cross back over the limit. 
    
    When you get the amp fault is the target gui also saying you've hit the hi 
    or low limit? You can fix the issue rather easily in the hall by manually 
    jogging the motor back over the limit, then running home to reset the 
    encoder value, this might also work from PDP using relative jogging?