Each of the following monitor points must report a nominal condition to the gas interlock panel in order for the logic to be "made up" and for gas flow to be enabled:
Label | Meaning | Likely Remedy | Sensor |
---|---|---|---|
Low Pressure | The seconeary | Check for a closed | 3 pressure |
Note: This channel | pressure of one or | "Excess Flow" Valve, | switches located |
will always indicate | more of the mixer | Remedy the cause, and | on the "Delivery |
a fault after some | inlet gas supplies | reset the valve | Rack" |
other problem has | has dropped below | Replace empty supply | |
caused the solenoid | the 45 psi | bottle. | |
valves to close. | threshold. | ||
Gas Shed Airflow | Gas Shed Exhaust | Restore forced | Vane Switch |
Fan ( ceiling of | ventilation. | mounted just | |
"Isobutane Room') | inside exhaust | ||
has failed. | fan | ||
Overtemp Gas Shed | Temperature in Gas | Take action to protect | Klixon mounted |
Shed Too High | equipment. | in rack | |
(110oF). | Reduce temperature. | ||
Over-Pressure FPP | VDC/FPP Exhaust | Eliminate exhuast line | PHOTOHELIC(R) |
Over-Pressure VDC | manifold pressure | blockage | gauges on gas |
Electron | at Hadron Or | Allow Hall-A | panels in shld |
Over-Pressure VDC | Electron Shield | atmospheric pressure to | houses |
Hadron | House Gas Rack | stabilize | |
Gas Leak | Flammable gas | Localize leak by | GASMASTER |
detection system | referring to readings on | HydroCarbon | |
has sensed a leak | GasMaster-4 system in | Detector heads in | |
Counting House | Gas Shed and | ||
Fix Leak | each Shield | ||
House. | |||
Overtemp Electron | Temperature in | Take action to protect | Klixon mounted |
Electron Shield | equipment. | in gas rack in | |
House Too High | Reduce temperature | Electron Shield | |
(110oF). | House | ||
Overtemp Hadron | Temperature in | Take action to protect | Klixon mounted |
Hadron Shield | equipment. | in gas rack in | |
House Too High | Reduce temperature. | Hadron Shield | |
(110oF). | House | ||
Post-Bubbler | Gas pressure out of | Reset Dynamass | Pressure switch |
Supply | mixer/bubbler rack | Controller | in rear of Mixing |
Overpressure | is >18 psi. | If needed, vent excess | Station |
pressure using MV-299 | (mixer/bubbler | ||
rack) |
Each Excess Flow Valve automatically closes if the flow rate through it exceeds about 4 slpm at 45 psig. The exact flow threshold varies somewhat depending upon the delivery pressure.
These valves must be manually reset after they trip. This is done by rotating the red handle 90o CW (to OPEN/RESET ) and then 90o CCW (back to AUTO SHUTOFF. ). It will be necessary to keep the valve in the OPEN/RESET position for about 10 seconds until nominal pressure builds up downstream. The excess flow valves must be returned to the AUTO SHUTOFF setting to insure system safety.
If the gas pressure in any enabled supply line to the mixer rack drops below about 40-45 psig, the interlock will sound an alarm and close all of the solenoid valves. This prevents the system from delivering a bad mixture to the detectors. After restoring the gas supply, for example, after replacing an empty gas cylinder, perform the following steps to restart the flow of gas.
Normally the gas control system is protected from power outages by an uninterruptable power supply (UPS). If the system is nevertheless disturbed by a loss of power then perform the steps outlined in section 3.2, Startup Procedure.