First check to see if you can fix the problem. Following are some frequently
encounted problems and how to deal with them. If you can not fix or are
not sure about it, you should call the cryotarget on-call person (listed on
the whiteboard in the counting house).
Cryotarget lifting are selected from the
`position' menu item on the `atarg' GUI.
To move the target, first call
MCC to have the beam turned off and mask FSD, as well as to
tell them what new target you are going to. Once the beam is
off and the FSD is masked, click the appropriate button corresponding to
the target you want in the Lifter GUI,
the target will start to move. While it is moving, the `busy' and the
`status' lights on the
Lifter GUI should light up. The encoder position in the
Lifter GUI and the GUI cartoon will also change.
It may
take a few minutes for the target to move to the new position. You're
there when the busy and status lights go out and the break light on, and the
green light goes on at the new position, and the encoder position has
reached the right value. When you're finished you call MCC again, have
them reset the FSD mask and give us back the beam.
First you should clear the software record by clicking on
CLEAR SLECETED RECORD. Try to move again. If still not working,
you can try to reboot IOC (see how to reboot the cryotarget IOC). This
solves the problem most of the time. If the problem is still there, next
you can try to restart the cryotarget GUIs (exit all the GUIs, then follow
How to start the GUIs from scratch). If the problem persist, you need to call
the cryotarget on-call person (listed on the whiteboard).
To service an alarm, first click the button on the Alarm GUI. This
launches an alarm tree GUI which lights up those elements in the tree
which have gone outside their limits. Go to the lowest, rightmost button
which is lit up and click on its name. { Always service alarms from the
lowest branch in the tree!} This will bring up another GUI which shows
the current value, the high and low alarm limits, and the more extreme
hihi and lolo alarm limits for each item in the category you just
clicked on. The offending items are highlighted. Jot down which item
is causing the alarm. If by this time it is still out of the alarm
limits you have a problem. Call one of the target contact people to
find out what to do. They may advise you to change the alarm limits,
but this should only be done or sanctioned by one of the target
experts/contacts (Chen, LeRose, Meekins, Keith).
The more usual
case is that the value has returned to its nominal value (such as the alarm due
to condition change caused by beam off/on). In that
case, all you have to do is click on the lit button in the leftmost
column and that'll take care of it. Continue doing this until all
alarms have been serviced.
You need to reboot the target IOC if the strip charts have flatlined,
and/or the heartbeat GUI has stopped beating, or some of the normal functions
stopped working (for example, you can not move the target). Don't panic,
the target
remains in PID mode even when the IOC has died. But you're running
blind until you reboot.
During the reboot, the PID mode goes off.
For the deuterium target, to prevent any potencial of freezing (freezing
temperature is 18.7 K), a constant auxillary power supply should be used
before robooting the IOC. For the helium and the hydrogen targets, you can
proceed directly to rebooting the IOC.
The first thing to do is inform the shift leader that you need to reboot
cryotarget IOC so the shift leader (or you) can
stop run.
For deuterium target only: Before you reboot, you have to supply a constant
auxillary power to the heaters.
You need to know approximately what the heater power is for the deuterium
loop when the beam is off. It is a good idea to
write this down when you started your shift.
The auxillary high power heater power supply
and the switch box are right above the Reset IOC button. Turn on the
deuteirum loop (usually loop 2)
power supply. Turn on the switch box power.
Dial in the appropriate setting for the power supply. You can proceed to
reboot the IOC.
To reboot ioc, open a web page, go to hareboot7. Log on as hlauser (password
on the wall in the counting house). Click on the iocha13. Then click on
CONTROL. Check both 5 and 6. In the pulldown manu, choose Reboot Immediately.
Click on Next. Then click on Apply. The ioc reboot will take a few minutes. During that time, when the ioc first comes back, you will hear some alarms.
Wait for a few minutes, all should go back to normal.
After that, check the high power heater to make sure it is in PID mode.
If it is not in PID mode after waiting for a few minutes, click `PID' to put
it in PID mode.
(For Deuterium target only: now it's the time to switch the auxillary heater
power supply back to the regular power supply). Check the fan and click
`update' button. Check the charts to make sure everything back to normal.
Service the alarms when things are settled down. When you are all done,
inform the shift leader that the cryotarget is ready.
Don't forget to log the target IOC reboot in halog.
To start the target control software, logon on to the target PC
poltarac under the poltar account,
you need to get the password during the training (also on the wall in
the counting house).
Type `cd Screens' to get to the correct directory, then launch
the software by typing `./tgtgui'. Don't put this in the
background, messages need to go to this window. The main target GUI
will appear.
Now on the main target GUI, click on the
`alarm' button. Click `OK' in the dialogue box,
ctarg.alh will get loaded and your alarm GUI will appear.
Launch the working loop GUI by clicking on that loop (loop 3 for LH2
for HAPPEX3). Click on `Chart' to get the displays.
Since the high power heater power is linked to the temperature in each
loop via a feedback (PID) mechanism, you can't affect the heater power
directly. To adjust the heater power, you adjust the JT valves.
Click on the JT valve button on the loop GUI. Set the step size to be
a small value (say, 0.5%).
Click on the J-T loop open (or close) button to change
the J-T valve value. You should do it slowly, say, no more than one
percent every 30 seconds). Watch
the high power heat value change in the loop chart.
Note that the high pwer heaters have upper limits associated
with them (set in the high power heater GUI). These upper limits
may prevent you from going as high as you want with the heater power,
if so change the limit. If you are not sure, contact the cryotarget on-call.
The fan speed (accessible from the FAN in the LOOP GUI) can be adjusted.
The nominal setting is 25% (of full speed)
which is 60~Hz (the tachometer should read back 60 Hz for normal
running).
In the regime we're operating in, a higher fan speed
actually raises the temperature a little due to the increased heat
load put out by the fan motor. The fan frequency may be lowered on
loops which will not be in the beam for long time (to 10% or 24 Hz). If you
put
them back into the beam you should raise the fan frequency back up to
60 Hz to mitigate local boiling.
The target operator should usually not need to open the Warm return
valve. Only in special situation when the cryotarget warmed up, the return
coolant is too warm (temperature higher than 30 K), the cryo-group
may want to close the cold return valve (which is controlled by the cryo-group). Then they will need us to open the Warm Return Valve (which is controlled by
us). In this situation, the cryotarget on-call should be called in. However, at the mean time you should comply with the request from cryo-group to open the
Warm Return Valve.
To open the Warm Return Valve, click 'device' on the atarg control GUI,
choose the Warm Return, which will open a new `Warm Return Valve' panel.
The value shown is the percentage open (0-100%). It should be a value near 0
(closed).
Every time click only ONCE on the `energize' button next to `7 Warm Return
Close'. Wait for the status
button go from red 0 to green 1 for a second and change back to red 0.
Watch the valve value. Now you can click again. The usual procedure is that
the cryo-group (or MCC) will close the Cold Return to 75%, then ask us to open
the Warm Return by 50%, and they will close the Cold Return to 25% and ask us
to fully open (100%) the Warm Return
and then they will fully close the Cold Return.
(Special Note: due to calibration problem, the readback value of the valve
openning is 0-40 instead of 0-100. 40 is fully open).
Back to cryotarget home page
Back to Hall A home page
Back to Jefferson Lab home page