Next: Target Enclosure & Windows
Up: Target Ladder & Motion
Previous: Description
  Contents
The motor can be controlled locally and remotely. Local control
is provided through the SmartStep 23 keypad controller. The keypad
allows the target to be jogged into position. It also allows for small
codes to be saved which will move the target ladder into preset target
positions. Remote control is provided through the EPICS environment.
During norml operation, target motion is controlled through the lifter
MEDM GUI running on one of the computers in the Hall A counting house.
The final GUI is under developemnt at this time, but it will have
buttons for preset target positions, as well as lights
indicating the status of the controller (i.e. any faults, at a limit, etc.).
The velocity, acceleration time, deceleration time and position can
also be manually set from the GUI, but the defaults should be correct
for all but special situations. The position of the motor is readback
on the GUI. This position is displayed in revolutions from the home
position and can be compared with preset target positions.
The electronics provide a Fast Shutdown (FSD) interlock signal
to the accelerator that is triggered whenever the target is moved with
the beam on. This prevents damage to the target
cell and ladder due to the electron beam. The FSD signal is generated
by the SmartStep controller and sent to an FSD node in the Hall.
Target changes require Hall A personnel to telephone MCC and request
temporary masking of this FSD channel.
Next: Target Enclosure & Windows
Up: Target Ladder & Motion
Previous: Description
  Contents
Xiaochao Zheng