Next: Maximum permissible exposure
Up: Laser Standard Operation Procedure
Previous: Off-normal and emergency procedure
  Contents
Several controls have been added as preventive measures to the laser room
and to the direct laser area. We will enumerate these controls here.
- The laser control area will have danger signs posted and will have a
yellow beacon indicating the presence of Class IV diode lasers. Danger sign will also be posted near the target enclosure area.
- A controlled access interlock system will limit the entrance to the laser hut with a coded number pad. The code is given only to the authorized
laser users listed in section 10 with currently valid training.
- The laser switches are interlocked to allow an opening of the door to
turn off the laser (to stand-by).
- The main power plug to the laser can be easily pulled. It is plugged
into a power strip with a on/off switch which can be easily switched off.
- Protective safety goggles (minimum OD 4.7 at 795 nm)
have to be worn when the laser is operational.
- All laser beam paths outside the laser hut are enclosed with beam pipe or
other enclosure (except during laser alignment process).
- All personnel need to fulfill the training requirements as indicated in Section 1 of this document.
- the LSOP will be posted on the outside door of the laser hut to inform
personnel about the
hazards associated with the setup and the proper procedures.
Next: Maximum permissible exposure
Up: Laser Standard Operation Procedure
Previous: Off-normal and emergency procedure
  Contents
Xiaochao Zheng