User name C. C. Chang
Log entry time 23:52:59 on March24,2001
Entry number 59270
keyword=Target control problem
At about 23:30 while beam went off due to power supply problem, target alarm
came on. The target temperature continued to drop down to about 15.5 K. Lingyan
turned the cooling down just to keep the temperature from dropping further. The
reason for the drop in temperature could be due to the stuck heater; the heater stuck
at about 100W level. Lingyan rebooted the target IOC. The target temperature was restored back to 19Kafter regaining heater control. We will keep an
eye on the target temperature when beam
comes back (we lost the beam due to power supply problem; there was no estimate
as to when beam will be back).