• Main INDEX
  • Monthly INDEX
  • PREV
  • NEXT

    User name folts

    Log entry time 19:42:58 on October 20, 2006

    Entry number 187779

    keyword=tech/cryo outage

    A cold compressor trip in ESR was the cause of the down.

    It recovered quickly but the right Q3 magnet did not. Took an access to look at the LL meter and found it good. asked the counting house to reboot Right HRS controls and LL problem cleared.

    Reset magnets and left the Hall

    NOTE: liquid level meters need to be labled better

    A copy of this log entry has been emailed to: fansler@jlab.org