User name folts
Log entry time 03:36:10 on June 13, 2009
Entry number 280929
keyword=tech/Quench reset
Called in for fault on right dipole and Q3 after quench. Q3 cleared after
diddling with the lever. It seems to be out of adjustment and would not
latch.
Dipole would fault on the GUI but no fault indicated on the power supply
or interlock rack. I cycled power on the Allen Bradley and waited….. and
reset the interlock rack. The controls became operational but the ramp
was slower than normal. I stopped the ramp and de-powered everything and
waited….. On start up the controls responded as they did on the original
fault. De powered the power supply with the switch on the power supply
and waited……. Re powered and reset the interlock rack. This time I got a
clunk in the power supply and the controls responded correctly
A copy of this log entry has been emailed to: fansler@jlab.org