keyword=Cause of Cryo-problem (copied from ELOG): the culprit of longer down time
I have copied the exact language from the ELOG entry (1503884) that I see
convincing for the cryo-problem we are facing since last night 10 PM so
that people can see it remotely:
Hall A target issue during the overnight hours was due to a return valve
on the Refrigeration Recovery Heat Exchanger (RRHX). Due to some unknown
event around 10 pm, the return valve on the RRHX went closed to prevent
cold gas from going back to compressor suction. Once the problem was
recognized and the recovery was almost complete, the ESR went down due to
C2 oil pump issues.