    User name A. Tobias

    Log entry time 19:18:41 on November20,2010

    Entry number 341045

    keyword=Target: Tweaked JT Valves after target change from LD2 to LH2

    I changed the fan speed for Loop 1 LD2 from 60Hz to 24Hz after we stopped running on this target. I tweaked the JT Valve from the nominal 33% down to about 18%.

    I changed the fan speed for Loop 2 LH2 from 24Hz to 46Hz since we are now running on LH2. I tweaked the JT Valve from 28% up to about 41%.

    I will fine adjust these JT Valve parameters as the target settles in during LH2 running on this shift.