User name Kelly
Log entry time 15:49:30 on June 9,2000
Entry number 43248
keyword=change to PID parameter
There a frequent trips with beam returning to 80 uA too quickly for target to
respond. Temperature rises to 19.8 K. We increased the PROP parameter in the
loop2 PID control from 600 to 700 hoping for more rapid heater response. Keep
an eye on this!