User name K. McCormick
Log entry time 19:48:20 on January26,2001
Entry number 55799
Followups:
keyword=New ESR variable added
A new variable has been added to the target GUIs that should be closely monitored.
It's called CTD6614 and it's the ESR temperature. It should not exceed 14.0K per
the ESR. Unfortunately, it hovers around 14 K usually when we're taking enough
coolant to run 80 mA, so I set the alarm limits at 14.1 K. If the alarm goes off then
decrease the beam current on target and close the JT Valve until the temp goes below 14.