keyword=Guideline for change LH2/LD2 fan frequency
Guideline for changing fan frequency (for target operator):
1) For LH2 loop:
When change from 10% to 25% or change back from 25% to 10%, please take steps
of 5%. After each step, wait for heat load to stablize then proceed to next step.
At the beginning and close to the end, smaller step will be a good idea. Use the
heat power change as an indicate (if the power change is abnormally high, say more
than 30 watts for 5% change, then you need to slow down. If not sure, call the
cryotarget-on-call).
2) For LD2 loop,
When change from 10% to 15%, take steps of 2%, 2% and 1%.
When change back from 15% to 10%, take 2% then 3%.