Log entry time 03:47:58 on March 23, 2005
Entry number 142238
keyword=tech
called in for Q2 overheat. 1600 amps seems OK for short periods but for
long runs it's on the hairy edge. Me and Dr Pete installed fans on top of
the power supplies to pull the heat through the PS from the bottom, this
is still working after 30 min. so we'll give it a try. This limit should
be noted for future experiments, we have already rebuilt the cooling
system for max flow and it seems to be flowing fine.There is just too
much heat in the box for LCW with this much delta T to remove at this
amount of flow.