    Log entry time 03:47:58 on March 23, 2005

    Entry number 142238

    keyword=tech

    called in for Q2 overheat. 1600 amps seems OK for short periods but for long runs it's on the hairy edge. Me and Dr Pete installed fans on top of the power supplies to pull the heat through the PS from the bottom, this is still working after 30 min. so we'll give it a try. This limit should be noted for future experiments, we have already rebuilt the cooling system for max flow and it seems to be flowing fine.There is just too much heat in the box for LCW with this much delta T to remove at this amount of flow.