    User name LeRose

    Log entry time 15:04:58 on June23,2005

    Entry number 147011

    This entry is a followup to: 147010

    keyword=Left Arm Back

    Quads have been cycled
    Re rebooting:
    On the web go to http://hareboot10
    username and password are on the wall
    select immediate reboot for iocha14 (where it says "no action")
    then press "apply".
    It will take several minutes for the reboot to complete. Be patient!
    When the screens come back to life Q2 and Q3 will be at zero and the dipole will be ramping down.
    Bring up the dipole power supply control screen and type in the set current you where running at before (666 amps for E94-107 production running)
    Then ramp Q2 and Q3 up to 1600 amps each (turn the power supplies on first).
    When both quads get to 1600 go to the tools screen and type in the P0 value you want (1.96 for production running on the left arm in E94-107).
    Then wait for the magnets to get to the correct settings.