User name Armstrong
Log entry time 13:41:12 on July30,2005
Entry number 150105
This entry is a followup to: 150102
keyword=Septa reset procedure note
We discover empirically:
after the septum IOC hangs and has to be reset (can be done
via hareboot), and after the IOC comes back to life and one gets screens such
as shown in
halog entry 150102
that you need to click the Power Supply CMD "ON" button to get
the temperatures to reset; then the Interlock Reset will clear
the Interlocks (assuming the temperatures are OK).
Moral: Don't just wait for the yellow crossed-out lines
on the temperature readouts to clear themselves, try the power
on button...