User name Jack
Log entry time 10:13:29 on October13,2005
Entry number 156728
keyword=Q2 and Q3 IOC reboot (both arms)
During the down we installed latching relays on the VMICVME-2210 in the iocha14 crate and the iocha16 crate (Left Arm and Right Arm). This should stop the Q2 and Q3 magnet power supplies from being turned off and their polarity set to the default value when the crates are reset. HOWEVER, the Q2 & Q3 currents will still be set to zero during an IOC reboot. So, the quads still need to be degaussed and then set to the appropriate currents. Someday this will get fixed, but not yet.