• Main INDEX
  • Monthly INDEX
  • PREV
  • NEXT

    User name J. Singh

    Log entry time 08:03:46 on October27,2005

    Entry number 158150

    keyword=recovering from right septum trip

    the lower coil is at 6.64K, the yoke is at 5.02K, and the upper coil is at 7.54K. since we are below 7.8K, we will start the recovery procedure.

    (1) turned off dump switch and power supply
    (2) reset interlocks, after a few secs, the interlocks cleared
    (3) turned on dump switch, after a few secs, the indicator turned green
    (4) turing on power supply, after a few secs, indicators turned green
    (5) set current to 316.92 A, after a few seconds, the current started to ramp up at 0.2 A/sec

    current on its way back up!


    FIGURE 1