Main INDEX
Monthly INDEX
PREV
NEXT
User name fansler
Log entry time 08:32:13 on February 09, 2007
Entry number 191681
Followups:
keyword=R_Q2_Liquid _Level_Trip
0800 I noticed the right Q2 was tripped on an interlock fault. Upon
further investigation, I discovered the liquid level was oscillating
between 7 percent and 90 percent. I called Pete, and requested he tune
the PID loop to overcome the oscillations. I reset the magnet and called
the counting house to request they reset current and ramp the magnet.
A copy of this log entry has been emailed to: fansler@jlab.org