    User name M. Stevens

    Log entry time 16:31:40 on April 03, 2007

    Entry number 197758

    keyword=Rt. Dipole new failure mode

    Yesterday morning the right dipole "locked up" and would not respond to either software generated commands or manual inputs through the power supply gui. It was stuck at 369 amps. We attempted the right dipole flying reset procedure using a local terminal (laptop) to no avail. The Dynapower Octaqgon computer would not return a ">" or echo characters. It would occasionally execute a command, such as RST, albeit with a time delay of at least several seconds. Troubleshooting revealed a dead RS-232/RS-485 converter module in the slow controls serial cross connect chassis in rack 1H75B05. We replaced the module, and everything worked normally.