    User name M. Stevens

    Log entry time 18:09:07 on June 26, 2007

    Entry number 206690

    keyword=Tech - ramp doors and smoke removal fans operation restored

    When we prepared to close the hall, the ramp doors would not close. Earlier today, we were unable to operate the smoke removal fans. We suspected the two problems were related, as these systems are interlocked. We found the fan circuit breakers in a stainless steel breaker panel on top of the hill, and they were not tripped. We contacted Paul Powers and Bob Rice and learned that the panel that feeds the panel on top of the hill is located next to the emergency generator behind the counting house. That panel is identified as MDP EM, and the breaker that feeds the fans/doors is breaker 10, which was tripped. Paul Powers reset the circuit breaker, and everything worked as advertised. Contact me if you want me to show you where this important breaker is located.