Main INDEX
Monthly INDEX
PREV
NEXT
Make New Entry,
Make Followup Entry
User name Jack (Techs)
Log entry time 12:11:53 on November 09, 2008
Entry number 247759
This entry is a followup to: 247730
keyword=Gas system shutdown
The nitrogen in the gas system ran out around 6AM. At that point the
pneumatic valves lost pressure and closed. Eventually the pressure
bleeds down in the argon and ethane lines and the VDC system will give a
"low pressure" alarm. While all the cylinders that were changed were
empty, what caused the trouble was that BOTH of the nitrogen cylinders
ran out. When they are replaced the NITROGEN PURGE VALVE needs to be
opened temporarily to charge the pneumatic valves. Once the pneumatic
valves are functional the bypass valve should be closed and one of the
nitrogen cylinders selected to be online. This was done around around
9AM. The only system this might be an issue for is the VDCs. The ethane
takes longer to bleed down than the argon. I see in the Archiver that
the argon and ethane mixing was shut down during this time except the
ethane was flowing from about 8:00 to 8:30, but no argon. So, there may
be a little change in the VDC operation. Flow was on and back to normal
at about 9AM.