    User name Jack (Techs)

    Log entry time 22:11:23 on October 22, 2009

    Entry number 296154

    This entry is a followup to: 296129

    keyword=RQ1 and LQ1 reset

    If the RQ1 or LQ1 show a "Spare" fault, this is a fault from the "Saclay" rack which handles the cryogenics faults. To clear this fault: go into the middle room, find the panels with the green pushbuttons, one button is labeled something like "Left Q1 Local Controls Reset" and another is labeled "Right Q1 Local Controls Reset", press the appropriate button for the count of about 5, check to see if the "Spare" fault cleared. If the fault cleared you should be OK. The other faults are cleared by pressing the buttons on the GUI.