keyword=Power outage: preliminary assessment at 8am meeting
At the 8am meeting today, the JLab experts seemed to think that both last
week's and today's power outage were caused by a ground fault in the
bunker where the power enters the accelerator site. The responsibility
for this unit lies with the power company. After the power failed this
morning, a smoking rotary switch was replaced in that bunker. Also some
fuses and loose contacts were fixed.