keyword=disabled right Q1 cryo alarms
Since right Q1 cryo is in alarming situation, keeping alarm handler "red", I disabled the cryo alarms for now to more easily see if anything else becomes alamring. They should be turned back on when the cryo gets brought back, presumably day shift 3/31.
This is done by going to the Alarm Handler window, clicking on 2nd line HacR_HPE1313A:0_Ch10 (and 3rd line ...Ch11 after), then menu "Action", option "Modify Mask Settings" and clicking on "Enable" button on 2nd line, "Enable/Disable Alarm".