AC Electrical Power for the HRS Shield Houses

All detector support frame AC power distribution is Class II. Work on AC electrical power distribution will be done in accordance with section 6220 of the Jefferson Lab EH&S Manual. Refer to the current copy of the Jefferson Lab EH&S manual for current lab policy.

The detectors will consume a fair amount of power, between 18kW and 30kW per spectrometer arm. The Shield Houses have AC power supplied from an isolation transformer mounted on the rear leg of the support gantry. The transformer is on the non-beam dump side of the gantry. This clean power is fed to a breaker panel mounted on the lower electronics platform of the Detector Support Frame. This panel is the large one mounted in the middle of the lower platform. Each relay rack has its own breaker panel which is fed from the main panel on the lower platform. There are thus two locations which can be used to disconnect AC power to the relay racks. Both panels should be checked in the event of a breaker trip. The feed for the isolation transformer is from a shunt trip breaker in a panel close to where the beamline enters the hall. The hall fire protection system will trip this breaker in the event of a fire in the Shield House.

One rack on the gantry platform, beneath the shielding house, has AC power supplied from a breaker in the panel mounted on the lower electronics platform of the Detector Support Frame. This rack houses the VME crate used for the Slow Controls of the spectrometer magnets.

The breaker panels for the two relay racks on the lower platform are located directly adjacent to the racks. They are mounted along the sides of the support frame and are directly accessible by a person standing at the front of each respective relay rack.

The breaker panels for the three relay racks on the upper platform are located along the side of the upper platform. They are in front of their corresponding rack and are accessible to a person standing at the front of the relay rack.

The breakers in the relay racks' panels control AC power to separate outlet boxes mounted in the rear of the relay racks. Careful attention should be paid to the labeling of breakers and which outlet they correspond to. Within each rack the spatial correlation is not direct.

As a general rule, in the event of a breaker trip the fault should be identified and corrected before AC power is restored to the circuit.

Notify qualified personnel in the event of a breaker trip which is not due to simple overloading of the circuit.

Personnel


The following personnel are qualified to address AC power distribution problems.
Back to Jack's Notes