User name brads
Log entry time 22:21:30 on August 06, 2006
Entry number 177792
This entry is a followup to: 177784
keyword=techs: R-HRS dipole current control frozen again
The R-HRS dipole current control is 'stuck' again. It stopped responding
at the same time the quad readbacks went white (log entry 177784) and did
NOT recover after that reboot (the quad readbacks are OK).
I just tried another reboot of the IOC to see if the dipole current
control would come back. It did not. The dipole looks like it is just
coasting to a value consistent with the last current setpoint of 119A.
This is pretty close to what we want for elastic kinematics...