Difference between revisions of "IOC reboot"

From Hall A Wiki
Jump to: navigation, search
(Feedback parameters)
 
(5 intermediate revisions by the same user not shown)
Line 1: Line 1:
IOC is iochacp - might need to reboot from the hall. Can try to connect via terminal server:
+
IOC is iochacp - might need to reboot from the hall.  
  
telnet cptsv1 2002 (update 11/7/2016 0 not sure this is true anymore)
+
No longer connected to terminal server. Can only reboot using remote power strip.
  
Also - crate connected to remote power strip - cptps2 (outlet 2). Call Dave/Alex for password.
+
hareboot4. Outlet 4
  
 
Before rebooting, make sure the cavity locking/unlocking script is OFF.
 
Before rebooting, make sure the cavity locking/unlocking script is OFF.
  
After rebooting, the quarter wave plate and half wave plate will probably be set incorrectly. Also, some power meter calibration factors need to be updated and the feedback parameters updated.
+
Note that the ioc communicates with the fiber amp via a portserver (hatsv43). If everything else is updating, but not the fiber amp, it might be that the portserver needs rebooting.
 +
 
 +
After rebooting, QWP1 will probably be set incorrectly (the HWP and QWP2 should not move). Check the position readback, and put it back where it was. The feedback parameters will also get reset - make sure to adjust them.
  
 
== Power meter calibrations ==
 
== Power meter calibrations ==
This needs updating
+
This needs updating - commands below are absolute.
 
# caput COMPTON_PW3R_S2_ca.B 7.9264
 
# caput COMPTON_PW3R_S2_ca.B 7.9264
 
# caput COMPTON_PW2R_S2_ca.B 11.833
 
# caput COMPTON_PW2R_S2_ca.B 11.833
Line 16: Line 18:
  
 
==Feedback parameters==
 
==Feedback parameters==
This needs updating
 
  
# caput COMPTON_SERVO_GAINao 148
+
# caput COMPTON_SERVO_GAINao 135
# caput COMPTON_SERVO_SEUILao 0.55
+
# caput COMPTON_SERVO_SEUILao 1
  
 
==Slow Ramp Parameters==
 
==Slow Ramp Parameters==
Line 26: Line 27:
  
 
==Initialize the QWP and HWP==
 
==Initialize the QWP and HWP==
 +
Needs updating
 +
 
# Send wave plates to 0 degrees
 
# Send wave plates to 0 degrees
 
# caput COMPTON_ORX_bo 1
 
# caput COMPTON_ORX_bo 1
Line 38: Line 41:
  
 
==Set exit line QWP==
 
==Set exit line QWP==
 +
This needs updating.
 
# Send QWP HOME
 
# Send QWP HOME
 
# caput COMPTON_ORY_bo 1
 
# caput COMPTON_ORY_bo 1

Latest revision as of 12:14, 25 July 2019

IOC is iochacp - might need to reboot from the hall.

No longer connected to terminal server. Can only reboot using remote power strip.

hareboot4. Outlet 4

Before rebooting, make sure the cavity locking/unlocking script is OFF.

Note that the ioc communicates with the fiber amp via a portserver (hatsv43). If everything else is updating, but not the fiber amp, it might be that the portserver needs rebooting.

After rebooting, QWP1 will probably be set incorrectly (the HWP and QWP2 should not move). Check the position readback, and put it back where it was. The feedback parameters will also get reset - make sure to adjust them.

Power meter calibrations

This needs updating - commands below are absolute.

  1. caput COMPTON_PW3R_S2_ca.B 7.9264
  2. caput COMPTON_PW2R_S2_ca.B 11.833
  3. caput COMPTON_LASERPCAV_ca.A 13630

Feedback parameters

  1. caput COMPTON_SERVO_GAINao 135
  2. caput COMPTON_SERVO_SEUILao 1

Slow Ramp Parameters

  1. caput COMPTON_SLOWRAMP_AMPLITUDE 0.02
  2. caput COMPTON_SLOWRAMP_PERIOD 180.0

Initialize the QWP and HWP

Needs updating

  1. Send wave plates to 0 degrees
  2. caput COMPTON_ORX_bo 1
  3. caput COMPTON_ORZ_bo 1
  4. wait 2 minutes
  5. caput COMPTON_PVAL_X_ao 11909
  6. caput COMPTON_PVAL_Z_ao 5725
  7. caput COMPTON_LMOVX_bo 1
  8. caput COMPTON_LMOVZ_bo 1

This should set the QWP angle to 47.63 degrees and the HWP to 22.9 degrees

Set exit line QWP

This needs updating.

  1. Send QWP HOME
  2. caput COMPTON_ORY_bo 1
  3. Wait 2 minutes
  4. Set angle to approximately equalize power in integrating spheres
  5. caput COMPTON_PVAL_Y_ao 11162
  6. caput COMPTON_RMOVY_bo 1