Difference between revisions of "Starting CODA for shift workers"
From Hall A Wiki
Line 12: | Line 12: | ||
*If needed use Rstart CODA components | *If needed use Rstart CODA components | ||
− | *In runcontrol make sure sbsts session | + | *In runcontrol make sure sbsts session and config GMN1 are chosen |
*To start a run | *To start a run | ||
Line 21: | Line 21: | ||
**hit Start Run button | **hit Start Run button | ||
**fill in run information in pop up box ( make sure you have correct target / runtype ) | **fill in run information in pop up box ( make sure you have correct target / runtype ) | ||
+ | |||
+ | *Pedestal run | ||
+ | **select GM1_pedestal config | ||
+ | **start run | ||
+ | **stop run after at least 30 k events | ||
+ | **go back to GMN1 configuration and start regular rub | ||
+ | |||
+ | *Troubleshooting | ||
+ | **SEB and ER stuck at end of run | ||
+ | ***hit reset in runcontrol | ||
+ | ***hit restart CODA components | ||
+ | ***redo configure and download | ||
+ | ***start a run | ||
+ | |||
+ | |||
+ | *if you are stuck check contact expert on slack ( in 4th desktop web browser ) or call DAQ on call ( number on slack channel on-call or on whiteboard) |
Revision as of 05:35, 12 October 2021
- DAQ should be running on hadesk4 in a VNC
- If the VNC is not opened, or after logging in as adaq
type : RunCoda
VNC password is adaq password
alternatively connect on vnc on adaq2:4
- Use CODA scripts buttons on first Desktop to start the ROC Xterms and Run Control
- If needed use Rstart CODA components
- In runcontrol make sure sbsts session and config GMN1 are chosen
- To start a run
- hit configure button in runcontrol, might need to hit it twice if vtpROC20 misses the first configuration
- hit download button
- check prescale factors ( To open prescale gui : ssh to sbs-onl@adaq2 and type prescale )
- hit Start Run button
- fill in run information in pop up box ( make sure you have correct target / runtype )
- Pedestal run
- select GM1_pedestal config
- start run
- stop run after at least 30 k events
- go back to GMN1 configuration and start regular rub
- Troubleshooting
- SEB and ER stuck at end of run
- hit reset in runcontrol
- hit restart CODA components
- redo configure and download
- start a run
- SEB and ER stuck at end of run
- if you are stuck check contact expert on slack ( in 4th desktop web browser ) or call DAQ on call ( number on slack channel on-call or on whiteboard)