next up previous contents
Next: 5.3.3.18  Troubleshooting Previous: 5.3.3.14  Safety Assessments

5.3.3.16  Operating procedure

All the operations are handled by computers. Some of them can be also performed independently by mechanical switches (referred as manually). In the following, the main window of the slow control program on the MacA or MacB display will be referred simply as the "main window".

Connection of MacB to MacA

The MacA and MacB communicate by the Timbuktu package, which implements the TCP/IP protocols over an Ethernet dedicated line.

The window that appears contains a `carbon copy' of the MacA screen: the user in counting room can control all the operations of MacA by using the MacB mouse and keyboard as if the MacB user were using the MacA; BE CAREFUL: the performance are reduced due to the connection: do not be in a hurry! wait for the screen to refresh after any action.

Startup of the system

The system startup depends on the history of the shutdown

After a normal shutdown procedure

After an emergency shutdown procedure

System shutdown

The normal procedure

The emergency procedure
This procedure is really an EMERGENCY procedure; do not use it for normal operation. Push the emergengy red button in front of the Left rack if you are in HAll A, the one in the counting room on the top of the computer monitor. In order to restart the system follow the startup procedure described above.

Waterfall activating

Empty target procedure
Put the slide in the right of the main window to the lower position, then switch off the pump; this can be done from the switch which is in front of Right Rack or from the switch which is in front panel of the "pump Command Module", in Counting Room (just over the MacB monitor); in both cases, the reactivating of the pump needs to be done from the same switch used to deactivate it (see "Waterfall Activating Procedure").

Target movement procedure

(Eventual) gas flow operating procedures

The gas filling of the target cell, when empty, has to be done in Hall A: on the right rack there is a self-eplaining panel. The washing button has to be pushed (for about 15 minutes) to open the inlet and outlet valves in order to allow the gas to replace the air which fills the target cell.

In order to refill the cell, in the case of very small leakages (remember that the pressure must be about 1.02 Atm), push the pressure bottom part of the main window. The pressure control window will appear. The operation is self-explaining. Just remember that the gas flows only if you keep the button pressed.

Calibration of the movement system
For `normal' operation the user does not need any additional information about the movement system. The following calibration tables (target and angle positions versus encoder values) are useful for checking purpose; notice that if the target changes, the calibration has to be performed again. The following values are OK for the waterfall, carbon, berillium, iron target which was installed in July '96.

The corrispondence between the targets and the encoders is as follow:

Target Encoder Position
Water 17301
Up Survey 38528
Carbon 42949
Berillium 47371
Iron 51792
Low Survey 56213

The vertical scale factor is: 1 encoder unit = 5.74 $\mu m$

The angular correspondence is:

Angle Encoder Position
0 degree 27361
30.533 degree 26479

that means: 1 encoder unit = 0.035 degree

When a new calibration is required[*] only an expert person must perform the following steps:


next up previous contents
Next: 5.3.3.18  Troubleshooting Previous: 5.3.3.14  Safety Assessments

10/13/1997