All the operations are handled by computers. Some of them can also be
performed independently by mechanical switches (referred to as
manually). In the
following, the main window of the slow control program running on
the MacA and/or MacB display will be referred to simply as
the "main window".
The MacA and MacB communicate through the Timbuktu package, which implements the TCP/IP protocols over an Ethernet dedicated line. To make the connection, following procedure outlined below:
CONTROL
button after you
entered the TCP/IP number (129.57.188.20
).
H2OCEBAF
and the password
WATER
.
The window that appears contains a `carbon copy' of the MacA screen:
the user in counting room can control all the operations of MacA by
using the MacB mouse and keyboard as if the MacB user were using the
MacA; BE CAREFUL: the performance is reduced due to the
connection: Be patient! wait for the screen to refresh after any
action.
The system startup depends on the history of the shutdown:
In the hall,
The first time the program is run, after MacA power on, it initializes the
electronic modules. Every time the program is run, it asks for a new
initialization of the electronic modules. Answer YES; a small window
with 4 buttons appears. Press all the buttons in order from top to bottom.
When the initialization is done the main window comes back.
This procedure is really an EMERGENCY procedure; do not use it for normal
operation.
Push the red button in front of the left rack if you are in the
hall, or the one in the counting room on the top of the computer monitor.
In order to restart the system follow the startup procedure described above.
From the counting house: use the slide on the right of the main window of MacB to set the pump speed to minimum, then switch off the pump by turning off the switch on the front panel of the "pump Command Module" which is located over the MacB monitor;
In the hall: one can set the pump speed to minimum either from MacA by using the slide on the right of the main window, or use the button on the front panel of the right rack, and then turn the pump switch on the right rack to ``off'' position.
The reactivating of the pump needs to be done from the same switch used
to deactivate it; see "Waterfall Activating Procedure".
After the slow control program H2OCEBAF97 is activated,
The gas filling of the target cell, when empty, has to be done in Hall A: on the right rack there is a self-explaining panel. The washing button has to be pushed (for about 15 minutes) to open the inlet and outlet valves in order to allow the gas to replace the air which fills the target cell.
In order to refill the cell, in the case of very small leakages
(remember that the
pressure must be about 1.02 Atm),
push the pressure bottom of the main window. The pressure control
window will appear. The operation is self-explaining. Just remember that
the gas flows only if you keep the button pressed.
For `normal' operation the user does not need any additional information about the movement system. The following calibration tables (target and angle positions versus encoder values) are useful for checking purposes; notice that if the target changes, the calibration has to be performed again. The following values are OK for the waterfall, carbon, beryllium, iron target which was installed in July '96.
Target | Encoder Position |
Water | 17301 |
Up Survey | 38528 |
Carbon | 42949 |
Beryllium | 47371 |
Iron | 51792 |
Low Survey | 56213 |
The vertical scale factor is: 1 encoder unit = 5.74
.
The angular correspondence is:
Angle | Encoder Position |
0 degree | 27361 |
30.533 degree | 26479 |
that means: 1 encoder unit = 0.035 degree
.
When a new calibration is requiredA1 only the expert(s) is(are) allowed to perform the following steps: