The gas mixture is delivered to gas distribution racks in the Hadron Spectrometer and the Electron Spectrometer. The transmission lines and the distribution plumbing have been designed as if the FPPs and VDCs were actually independent systems using different gas mixtures. This design was chosen in order to ease the expected transition to such a system in the future. Also supplied is a source of purge gas, currently pure argon. The distribution racks provide, for each detector, selection of either operating gas or purge gas, flow control and metering, overpressure relief to protect the detector components, exhaust flow measurement, and backflow prevention.
The Excess Flow Valves automatically close if the flow rate exceeds about 4 slpm at 45 psig. These valves must be manually reset after they trip. Refer to the section Resetting a closed Excess Flow Valve for this procedure The solenoid valves are electrically operated (24 VDC) normally-closed valves. Power must be supplied to the solenoids in order for gas to flow. Valve power is supplied, when interlock conditions are satisfied, by the Gas Interlock System. Note that one of the required interlock conditions is that there be ample gas pressure downstream of the solenoid valves. System operators must use the manual "Low Pressure Override" pushbutton on the interlock panel (in the mixing room) in order to initially bring up the 45 psig supply pressure. The pushbutton circuit automatically re-arms after ample pressure is detected by the pressure switches (PS-111, -112, -113). These switches are located immediately above gauges PG-131, -132, and -133. Just below these gauges are overpressure relief valves (RV-121, -122, -123) which have been set to release if the supply pressure exceeds about 60 psig. After passing through check valves which prevent backstreaming the three gas supplies enter the mixing system.