- The oven controller and temperature and flow displays are located
in a 19'' chassis in one of the racks upstairs. Make sure power to this
chassis is on. The green light on the front panel should be lit.
- Verify the alarm set points for the flow meter and
temperature indicator. Press the SETPTS button
until the display shows SP3. After about 1 second,
the setpoint value appears. It should be 250 for the
air flow display and 220 for the temperature display. Press
SETPTS again and check setpoint SP4. It
should be identical to SP3.
To change
any of the values use the MIN and MAX buttons. The MIN
button selects the digit to be changed whereas the MAX
button changes the value of the currently selected digit.
Press SETPTS again to store the new value.
When finished, press SETPTS until RUN appears in the
display.
- Verify the current temperature of the oven. It is shown
in the upper (red) display of the temperature controller
and is labeled PV for ``Process Value''. The units are C.
The value should be reasonable,
e.g. around room temperature if the oven has been off
for several hours or more. If the value does not make sense,
either the controller is misconfigured (see below) or the RTD
in the oven is broken or incorrectly connected.
Do not proceed before you have a sensible reading.
- (Optional) Verify the correct configuration of the controller.
Use the MENU button on the controller to scroll through
the various configuration menus. To inspect parameters within
a menu, press ENTER followed by MENU again. The suggested
default parameters are listed in Tables
and . This step
is time-consuming and can be skipped if you are relatively certain
that the configuration is ok. A detailed description of the
controller parameters is given in the controller manual.
- Verify that air is flowing. The air flow readout should indicate
a value of 350-450. These are arbitrary units. As long as the heater is
off, the reading should not fluctuate by more than about units.
- Verify the current temperature of the heater. It should be
close to room temperature. If the value is unreasonable, either
the readout is misconfigured or the thermocouple is broken.
Do not proceed before the problem is corrected.
- Verify that alarms are reset.
Underneath the main display there are four LEDs, one for each
alarm 1-4. If either LED 3 or 4 is on on either
instrument, it indicates that an alarm has been triggered and
that the system is interlocked. You must reset the alarms before
you can continue. To do so, first correct
the problem (e.g. turn the air flow on) then press RESET
once on the affected instrument(s). If the LEDs stay on despite
correct setpoints and readings, the instrument is probably misconfigured.
- Begin heating.
To avoid damage to the oven, the temperature must be increased
to the final value slowly. A good final operating temperature is
170C, and a good ramping rate is 60C/h, i.e. heating of the oven will take about three hours to complete.
In manual mode, you must enter a new temperature setpoint by hand
at fixed time intervals. (``Ramp and Soak'' does not seem to work reliably
with this controller.) You should increase the value by
10C every 10 minutes. For example, if the current oven temperature
is 35C, start with a setpoint of 45C and increase this
value by 10C in approximately 10 minute intervals.
To enter a new setpoint, do the following
- Press MENU on the temperature controller.
A little green light marked SP1 in the upper left corner of
the display will start to blink. Also, the first digit of
the green numerical display, labeled SV for ``Setpoint
Value'', will blink.
- Use MIN to select the digit you wish to change and MAX
to modify the value.
- When done, press ENTER. The display will briefly show
run when the controller enters normal operating mode.
This starts the heating process.
- Check correct operation of the controller. A little green
light marked SP1 in the upper left corner of the
temperature controller display indicates that the heater is active.
This light should blink slowly, being mostly on while the oven is heating
up and being mostly off (or even completely off for periods of up
to a few minutes) when the oven temperature has reached the setpoint.
The heater temperature should increase proportionally to the
fraction of time that the SP1 indicator is on.
Note that the temperature reading is not directly related to the
oven temperature. In particular, the heater may become significantly
hotter than the oven, and its temperature
might fluctuate from almost room temperature
to high values over short periods of time as the heater
power is automatically
cycled on and off by the controller. As long as the temperature
stays below the alarm threshold (220C) there is no reason
for concern.
- Check stability of the final temperature.
The temperature might overshoot slightly. If the overshoot is
less than about 5C then this is normal. If the stability is
poor it is probably due to incorrectly set PID parameters in the controller.
Changing these parameters is best done by an expert since this requires
in-depth understanding of the system.
The laser contributes significantly to the heating of the oven.
Therefore, you will notice sudden temperature instabilities when
the laser is turned off or on. It will take several minutes for
the controller to compensate for such changes.
- The air flow rate is slightly dependent on the heater power
applied (conductance varies with temperature).
Therefore, the flow rate will fluctuate by some 10-20%. This is
normal.
- At any time you can place the controller in standby mode by pressing
ENTER twice. The display will show a blinking text STBY.
This will turn the heater off completely and can be used
when the system appears to malfunction. However, exercise some
caution if the oven is at an elevated temperature since it will quickly
cool down if heater power is disabled and you will lose time bringing
it back up to operating temperature.
- In an emergency, simply turn the power to the chassis off completely.
This will open the interlock loops, thereby cutting power to the heater
and placing the laser in standby mode.