next up previous contents
Next: Remote Operation Up: Operation Previous: Operation   Contents

Local Operation

A brief description of the manual operating procedure is given here:

  1. The oven controller and temperature and flow displays are located in a 19'' chassis in one of the racks upstairs. Make sure power to this chassis is on. The green light on the front panel should be lit.

  2. Verify the alarm set points for the flow meter and temperature indicator. Press the SETPTS button until the display shows SP3. After about 1 second, the setpoint value appears. It should be 250 for the air flow display and 220 for the temperature display. Press SETPTS again and check setpoint SP4. It should be identical to SP3.

    To change any of the values use the MIN and MAX buttons. The MIN button selects the digit to be changed whereas the MAX button changes the value of the currently selected digit. Press SETPTS again to store the new value. When finished, press SETPTS until RUN appears in the display.

  3. Verify the current temperature of the oven. It is shown in the upper (red) display of the temperature controller and is labeled PV for ``Process Value''. The units are $^\circ$C. The value should be reasonable, e.g. around room temperature if the oven has been off for several hours or more. If the value does not make sense, either the controller is misconfigured (see below) or the RTD in the oven is broken or incorrectly connected. Do not proceed before you have a sensible reading.

  4. (Optional) Verify the correct configuration of the controller. Use the MENU button on the controller to scroll through the various configuration menus. To inspect parameters within a menu, press ENTER followed by MENU again. The suggested default parameters are listed in Tables [*] and [*]. This step is time-consuming and can be skipped if you are relatively certain that the configuration is ok. A detailed description of the controller parameters is given in the controller manual.

  5. Verify that air is flowing. The air flow readout should indicate a value of 350-450. These are arbitrary units. As long as the heater is off, the reading should not fluctuate by more than about $\pm 10$ units.

  6. Verify the current temperature of the heater. It should be close to room temperature. If the value is unreasonable, either the readout is misconfigured or the thermocouple is broken. Do not proceed before the problem is corrected.

  7. Verify that alarms are reset. Underneath the main display there are four LEDs, one for each alarm 1-4. If either LED 3 or 4 is on on either instrument, it indicates that an alarm has been triggered and that the system is interlocked. You must reset the alarms before you can continue. To do so, first correct the problem (e.g. turn the air flow on) then press RESET once on the affected instrument(s). If the LEDs stay on despite correct setpoints and readings, the instrument is probably misconfigured.

  8. Begin heating. To avoid damage to the oven, the temperature must be increased to the final value slowly. A good final operating temperature is 170$^\circ$C, and a good ramping rate is 60$^\circ$C/h, i.e. heating of the oven will take about three hours to complete.

    In manual mode, you must enter a new temperature setpoint by hand at fixed time intervals. (``Ramp and Soak'' does not seem to work reliably with this controller.) You should increase the value by 10$^\circ$C every 10 minutes. For example, if the current oven temperature is 35$^\circ$C, start with a setpoint of 45$^\circ$C and increase this value by 10$^\circ$C in approximately 10 minute intervals.

    To enter a new setpoint, do the following

    1. Press MENU on the temperature controller. A little green light marked SP1 in the upper left corner of the display will start to blink. Also, the first digit of the green numerical display, labeled SV for ``Setpoint Value'', will blink.
    2. Use MIN to select the digit you wish to change and MAX to modify the value.
    3. When done, press ENTER. The display will briefly show run when the controller enters normal operating mode. This starts the heating process.

  9. Check correct operation of the controller. A little green light marked SP1 in the upper left corner of the temperature controller display indicates that the heater is active. This light should blink slowly, being mostly on while the oven is heating up and being mostly off (or even completely off for periods of up to a few minutes) when the oven temperature has reached the setpoint.

    The heater temperature should increase proportionally to the fraction of time that the SP1 indicator is on. Note that the temperature reading is not directly related to the oven temperature. In particular, the heater may become significantly hotter than the oven, and its temperature might fluctuate from almost room temperature to high values over short periods of time as the heater power is automatically cycled on and off by the controller. As long as the temperature stays below the alarm threshold (220$^\circ$C) there is no reason for concern.

  10. Check stability of the final temperature. The temperature might overshoot slightly. If the overshoot is less than about 5$^\circ$C then this is normal. If the stability is poor it is probably due to incorrectly set PID parameters in the controller. Changing these parameters is best done by an expert since this requires in-depth understanding of the system.

    The laser contributes significantly to the heating of the oven. Therefore, you will notice sudden temperature instabilities when the laser is turned off or on. It will take several minutes for the controller to compensate for such changes.

  11. The air flow rate is slightly dependent on the heater power applied (conductance varies with temperature). Therefore, the flow rate will fluctuate by some 10-20%. This is normal.

  12. At any time you can place the controller in standby mode by pressing ENTER twice. The display will show a blinking text STBY. This will turn the heater off completely and can be used when the system appears to malfunction. However, exercise some caution if the oven is at an elevated temperature since it will quickly cool down if heater power is disabled and you will lose time bringing it back up to operating temperature.

  13. In an emergency, simply turn the power to the chassis off completely. This will open the interlock loops, thereby cutting power to the heater and placing the laser in standby mode.


Table: Suggested default parameters for the temperature controller.
Menu Submenu Setting
Output Redirection   S1.o1
Input Type   RTD
  RTD Type 385.3
  RTD Value 100_
RDG Configuration Decimal Point FFF.F
  Temperature Units $^\circ$C
  Filter Constant 0004
Alarm 1   Enabled
  Type Absolute
  Latched Latched
  Contact n.c.
  Setup Above
  Power On Enabled
  Low Value (anything)
  Hi Value 210.0
Alarm 2   Not Installed
Loop Break   Disabled
Output 1 Self Disabled
  % Low 0000
  % High 0095
  Control Type PID
  Action Type Reverse
  Auto PID Disabled
  Adaptive Control Disabled
  Anti Integral Enabled
  Start PID Disabled
  Proportional Band 0038
  Reset Setup 0050
  Rate Setup 0000
  Cycle Time 0001
  Damping Factor 0001
Output 2 (any) (anything)



Table: Suggested default parameters for the temperature controller (continued).
Menu Submenu Setting
Ramp & Soak Ramp Disabled
  Soak Disabled
Analog Output   Not installed
Communication Option Baud 9600
  Parity Odd
  Data Bits 7bit
  Stop Bits 1bit
Bus Format Checksum no
  Line Feed no
  Echo no
  Standard 232C
  Mode Command
  Separator Space
Data Format Status yes
  Reading yes
  Peak no
  Valley no
  Unit yes
  ID no
Address Setup (any) (anything)
Transmit Time (any) (anything)
Remote Setpoint   Not installed



next up previous contents
Next: Remote Operation Up: Operation Previous: Operation   Contents
Xiaochao Zheng 2001-06-01