Next: Safety Considerations
Up: Target Cell Heater
Previous: Target Cell Heater
  Contents
Figure shows a schematic diagram of the heater system
and the associated controls. Pressurized dry and filtered air at room
temperature is provided by a dedicated compressor in the Hall. The air
enters the system through a shut-off valve and a pressure regulator,
which is typically set to an output pressure of 15 psi. The flow rate
is measured with a gas velocity sensor (Omega model FMA-905) connected
to a display unit (Omega DP41-E-S2R) that provides an alarm
to indicate insufficient flow. The air then passes through a
resistive heater element (120 VAC, 700 W) and continues through
insulated copper tubing into the target oven. The
oven material is Torlon and Vespel plastic which can withstand a
temperature of at least 260C continuously.
The air finally exits the system through a several meters long
exhaust pipe where it can cool down.
Figure:
Schematic diagram of the target cell oven control system. The
instruments in the dashed box are located upstairs, while the remaining
components are located in the Hall in the vicinity of the target.
For clarity, the interlock circuitry
is not shown (see Figure ).
|
Figure:
Schematic diagram of the oven heater interlock system.
The switches represent relays.
In normal operation, the relays are energized (contacts closed).
An alarm condition
(or instrument power failure) will de-energize (open)
the corresponding relays, interrupting the interlock circuit.
The instruments are programmed such that their dual alarm outputs
operate simultaneously.
|
A 100 Pt RTD (Omega model F3105) measures the temperature
inside the oven. A process
controller (Omega CN77540-C2) operating in PID mode drives the
heater via a solid-state relay (SSR) regulating the heater power
dependent on the temperature detected by the RTD.
The SSR (Omega model SSR240DC10) accepts a low-voltage (3 32 VDC)
control signal of about 30 mA. A mechanical relay between the SSR and
the heater allows interruption of the 120 VAC heater power in case of a
malfunction (see section ).
A thermocouple (Omega 5SC-GG-K-30-36) is mounted on the
tubing right after the heater to allow monitoring of the temperature
of the air exiting the heater. Another display unit (Omega
DP41-TC-S2R) reads the thermocouple and generates an alarm if the
temperature exceeds a preset threshold.
The PID controller as well as the two display units are installed
in a 19'' chassis in the electronics racks on the second floor of the
counting house where they can be manually operated if necessary.
All other components are located in the Hall in the vicinity of the
target. The instruments can be monitored
and programmed remotely via serial RS-232 communications, which
allows convenient control via an EPICS/MEDM graphical user interface
(GUI) in the counting house.
Next: Safety Considerations
Up: Target Cell Heater
Previous: Target Cell Heater
  Contents
Xiaochao Zheng
2001-06-01